Group escalations
Also known as alert storm suppression
Overview
If many alarms are triggered within a short period of time, this can lead to a flood of notifications. To avoid this, alarms can be combined within an escalation. In this process, multiple incoming alarms are merged into a single escalation message — depending on individually defined conditions. In addition, certain alarm tags can be excluded from combining so that they continue to be escalated individually.
Procedure

Click on Engineering [A]
Click on Escalation [B]
▷ The overview of the escalation configurations opens.
Click on [D] ▷ The window opens Combining alarms [D1].
Activate the switch [D2], to enable combining alarms.
Enter under [D3] enter the period in seconds within which the alarms must occur in order to be combined.
Enter under [D4] the minimum number of alarms that must occur within the defined period for them to be combined.
Select under [D5] exclude the alarm tags that should be excluded from combining (e.g. High Prio).
Click on Save [D6], to apply the changes.
Example
Conditions:
Period: 10 seconds
Minimum number: 5 alarms
Scenario 1: Within 8 seconds, 5 alarms are triggered without excluded tags → The alarms are combined and sent as one escalation message.
Scenario 2: Within 10 seconds, 4 alarms are triggered → No combination, 4 separate escalation messages are sent.
Scenario 3: Within 10 seconds, 7 alarms are triggered, 2 of them with the tag High Prio (excluded) → The 5 remaining alarms are combined, the 2 High Prio-alarms are escalated individually.