Add and Configure Attributes

Add attributes to an asset template to define its datapoints, such as power measurements or operating states. Use the attribute editor to configure their units, historical recording, translated titles, analytics defaults, Augmented Reality (AR) position, and displayed value text.

All five tabs belong to the same attribute configuration:

Prerequisites

  • You have write access to Asset Modeling.

  • You have created an asset template that you can edit.

  • For conversions, configure the attribute's Class and Default unit in General first.

  • For historical analysis, enable Trending mode in General.

Open or Add an Attribute

Current Asset Core template details with Platform Core navigation and the Template button beside Attribute templates marked
Open a template attribute or add one from the Attribute templates list.
  1. Open Platform Core [A].

  2. Select Asset Core.

  3. Open the asset template.

  4. Select Template [B] beside Attribute templates. ▷ The attribute editor opens on General.

To configure an existing attribute instead, select its name under Attribute templates.

Switching tabs keeps your unsaved changes in the form; it does not save them. Select Save to apply attribute settings. If you select Back with unsaved changes, choose Keep Edit to continue or Leave Without Saving to discard them. Custom conversion changes have a separate save process, described under Conversions.

General

Use General to define the datapoint and how its values are handled. The figure shows an existing analog power attribute with the power class, kW as its default unit, and historical recording enabled.

General tab with the value type, attribute name, class, default unit, trending control, and Save marked
General settings for an existing template attribute.
Reference
Setting
Purpose

[A]

Platform Core

Navigation to Asset Core and its asset templates.

[B]

Asset value type

Select Analog for numerical measurements, such as power, or Digital for two-state signals, such as 0 and 1.

Virtual

Enable a datapoint calculated from other attributes. Enter a Default calculation before saving a virtual attribute.

[C]

Attribute

Enter the technical attribute name when creating it. The name is required and cannot contain ., {, }, [, or ].

Subtype

Select Input for incoming data, Output for outgoing commands, Status for state information, or Information for descriptive data.

[D]

Class

Classify the attribute, for example as power. The class determines available units and affects which functions are available.

[E]

Default unit

Select the unit of the attribute's values, for example kW. The choices depend on Class. Changing the class clears the selected unit, so select the unit again.

Default calculation

Enter an expression to scale, convert, or calculate values. See The Calculator for syntax and examples. Reset by default restores this field's initial value.

[F]

Trending mode

Enable historical recording when you need trends or historical analytics. Select On change to store changed values or Always to store every value, including repeated values.

Limit low, Limit high, Step size

Enter optional lower-limit, upper-limit, and increment settings. For example, 0, 1000, and 10 describe a range from 0 to 1000 with increments of 10.

[G]

Save

Apply the attribute settings.

Attribute and Subtype are set when you create the attribute and are read-only when you reopen it. Use Title language to provide translated display titles.

To add an attribute:

  1. Select General.

  2. Select the Asset value type [B].

  3. Enter the Attribute name [C].

  4. Select its Subtype.

  5. If applicable, select a Class [D].

  6. If applicable, select its Default unit [E].

  7. Select Save [G]. ▷ The new attribute appears under the template's Attribute templates.

Open the saved attribute again to configure the other tabs. When you save changes to an existing attribute, the editor stays open.

Conversions

Use Conversions to display values in another unit, as a cost, or as an emissions equivalent in Insight Analytics. The attribute's Default unit is the source unit. For example, a kWh-to-MWh conversion displays 1000 kWh as 1 MWh without changing the recorded readings.

Conversions tab for an energy attribute with preconfigured unit conversions and custom cost and emissions ranges
Conversion list and controls for a kWh attribute.
Reference
Element
Meaning

[A]

Conversions

Open the conversions for this attribute's source unit, grouped under Unit conversions, Cost, and Emissions.

[B]

Default unit

Check the source unit. Configure and save it in General first.

[C]

Preconfigured conversion

Inspect its Unit, Active dates, and Formula. The example converts kWh to MWh using x × 0.001.

[D]

Custom cost range

Apply a rate to express values in a currency. The EUR example uses a factor of 0.18 per kWh.

[E]

Create custom conversion

Open the dialog to add a conversion or another validity range.

[F]

Pencil icon

Open a custom range for editing, change its settings in the dialog, then select Save.

[G]

Delete icon

Delete the custom range immediately, without confirmation. Deleting its last range also removes the custom conversion.

[H]

Custom emissions range

Apply a factor to express values in the configured emissions unit. Use an appropriate destination unit and approved factor for your calculation.

Custom Conversion Settings

  1. Select Create custom conversion [E] in the conversion list. ▷ The Custom conversion dialog opens.

  2. Enter the conversion settings using the field reference below.

  3. Select Save [G] in the dialog. ▷ The saved range appears in the corresponding conversion group.

Custom conversion dialog with Unit, Purpose, validity dates, Factor, Offset, Save, and Cancel marked
The same fields configure a new conversion or an existing custom range.
Reference
Dialog field or control
What to enter or do

[A]

Unit

Select the destination unit, such as MWh, a currency for cost, or an appropriate emissions unit.

[B]

Purpose

Select Unit conversion, Cost, or Emission to determine where the conversion is offered in Analytics.

[C]

Active from

Enter the first date on which the range applies.

[D]

Active to

Enter the last date on which it applies, on or after Active from. Both endpoints are included.

[E]

Factor

Enter the positive multiplier for the source value. For a cost conversion, enter the rate per source unit. The initial value is 1.

[F]

Offset

Enter the constant added after multiplication; leave 0 when no offset is needed.

[G]

Save

Save the conversion directly; the attribute page's separate Save is not required.

[H]

Cancel

Close the dialog without saving its changes.

The calculation is result = value * factor + offset. For example, a factor of 0.18 and offset of 0 convert 1000 kWh to 180 EUR. The figures show demonstration settings, not recommended tariffs or emissions factors.

To add a later rate, use Create custom conversion again with the same Unit and Purpose and a new, non-overlapping date range. For consecutive periods, end one on 31 December and start the next on 1 January. If dates overlap an existing range, adjust them or edit that range instead.

Title language

Use Title language to provide display titles in different interface languages without changing the technical Attribute name. For example, the same power attribute can have the English title Power and the German title Leistung.

Title language tab with Translation, an English title, a translation's delete icon, and Save marked
Translated titles for one template attribute.
  1. Select Title language.

  2. Select Translation [A]. ▷ A language selector and title field are added under Title language and text.

  3. Select the language for the row.

  4. Enter its translated title [B].

  5. Repeat steps 2-4 for each additional language.

  6. Select Save [D]. ▷ The translated titles are saved on the attribute.

To remove a title, select the row's delete icon [C], then select Save [D]. Each language can be selected once.

Pipeline & AR

Use Pipeline & AR to set preferred analytics aggregation settings and choose the attribute's position in the Augmented Reality display.

Pipeline and AR tab with Mode, Function, Interval, AR Position, and Save marked
Preferred analytics aggregation and Augmented Reality position.

Aggregation Defaults

Pipeline raster provides preferred settings for new Insight Analytics datapoint series. For example, use an hourly average for a temperature measurement instead of selecting the same aggregation each time you add it to an analytic.

Reference
Setting
When to use it

[A]

Mode: None

Leave the preferred mode unspecified for new analytics series.

[A]

Mode: Current value

Start new series with recorded values rather than aggregated values.

[A]

Mode: Aggregated value

Start new series with values calculated over a defined interval. Function and Interval become available.

[B]

Function

Choose an aggregation appropriate to the measurement. For example, Average summarizes temperature over each interval.

[C]

Interval

Choose the time window for each aggregated value. For example, H1 represents one hour. Shorter intervals retain more detail; longer intervals give a coarser view.

  1. Select Pipeline & AR.

  2. Select a Mode [A] under Pipeline raster.

  3. If you select Aggregated value, select a Function [B].

  4. If you select Aggregated value, select an Interval [C].

  5. Select Save [E]. ▷ The preferred aggregation settings are saved on the template attribute.

When you add a new datapoint series to an analytic, Insight Analytics reads these preferences. Updating template defaults leaves settings already configured on existing series unchanged.

You can override Mode, Function, and Interval for an individual series in the Summary Table. This changes the analytic's series settings, not the template defaults. See Aggregations for the aggregation functions.

Configure historical recording separately under Trending mode in General. Aggregation defaults do not replace the trending configuration.

AR Position

Use Select position [D] under AR Position to choose where the attribute appears in the Augmented Reality display.

Option
Use

No Position

Leave the attribute without an assigned AR position.

Top

Show the attribute at the top.

Bottom Left

Show the attribute at the bottom left.

Bottom Right

Show the attribute at the bottom right.

  1. Select the position [D].

  2. Select Save [E]. ▷ The AR position is saved on the attribute.

Value mapping

Use Value mapping to display readable text for numerical values or ranges. For example, show Idle or Running instead of a raw number.

Value mapping tab with Mapping, the numeric upper limit, result text, delete icon, and Save marked
Value mappings with upper limits of 0 and 1000.

Each numeric entry is an inclusive upper limit. The displayed text comes from the smallest configured limit greater than or equal to the actual value.

Enter value
Enter result
Displayed range in this example

0

Idle

Values less than or equal to 0.

1000

Running

Values greater than 0 and less than or equal to 1000.

For these settings, both 750 and 1000 display Running. A value above 1000 is displayed numerically because it exceeds the highest configured limit. Mapping controls displayed text; use Conversions to convert units.

  1. Select Value mapping.

  2. Select Mapping [A]. ▷ A row with Enter value and Enter result is added.

  3. Enter the numeric upper limit [B].

  4. Enter the text to display [C].

  5. Repeat steps 2-4 for each additional range.

  6. Select Save [E]. ▷ The value mappings are saved on the attribute.

To remove a range, select its delete icon [D], then select Save [E].

Next Steps

Last updated