Add and Configure Attributes
Add attributes to an asset template to define its datapoints, such as power measurements or operating states. Use the attribute editor to configure their units, historical recording, translated titles, analytics defaults, Augmented Reality (AR) position, and displayed value text.
All five tabs belong to the same attribute configuration:
Prerequisites
You have write access to Asset Modeling.
You have created an asset template that you can edit.
For conversions, configure the attribute's Class and Default unit in General first.
For historical analysis, enable Trending mode in General.
Open or Add an Attribute

Open Platform Core [A].
Select Asset Core.
Open the asset template.
Select Template [B] beside Attribute templates. ▷ The attribute editor opens on General.
To configure an existing attribute instead, select its name under Attribute templates.
General
Use General to define the datapoint and how its values are handled. The figure shows an existing analog power attribute with the power class, kW as its default unit, and historical recording enabled.

[A]
Platform Core
Navigation to Asset Core and its asset templates.
[B]
Asset value type
Select Analog for numerical measurements, such as power, or Digital for two-state signals, such as 0 and 1.
Virtual
Enable a datapoint calculated from other attributes. Enter a Default calculation before saving a virtual attribute.
[C]
Attribute
Enter the technical attribute name when creating it. The name is required and cannot contain ., {, }, [, or ].
Subtype
Select Input for incoming data, Output for outgoing commands, Status for state information, or Information for descriptive data.
[D]
Class
Classify the attribute, for example as power. The class determines available units and affects which functions are available.
[E]
Default unit
Select the unit of the attribute's values, for example kW. The choices depend on Class. Changing the class clears the selected unit, so select the unit again.
Default calculation
Enter an expression to scale, convert, or calculate values. See The Calculator for syntax and examples. Reset by default restores this field's initial value.
[F]
Trending mode
Enable historical recording when you need trends or historical analytics. Select On change to store changed values or Always to store every value, including repeated values.
Limit low, Limit high, Step size
Enter optional lower-limit, upper-limit, and increment settings. For example, 0, 1000, and 10 describe a range from 0 to 1000 with increments of 10.
[G]
Save
Apply the attribute settings.
To add an attribute:
Select General.
Select the Asset value type [B].
Enter the Attribute name [C].
Select its Subtype.
If applicable, select a Class [D].
If applicable, select its Default unit [E].
Select Save [G]. ▷ The new attribute appears under the template's Attribute templates.
Open the saved attribute again to configure the other tabs. When you save changes to an existing attribute, the editor stays open.
Conversions
Use Conversions to display values in another unit, as a cost, or as an emissions equivalent in Insight Analytics. The attribute's Default unit is the source unit. For example, a kWh-to-MWh conversion displays 1000 kWh as 1 MWh without changing the recorded readings.

[A]
Conversions
Open the conversions for this attribute's source unit, grouped under Unit conversions, Cost, and Emissions.
[C]
Preconfigured conversion
Inspect its Unit, Active dates, and Formula. The example converts kWh to MWh using x × 0.001.
[D]
Custom cost range
Apply a rate to express values in a currency. The EUR example uses a factor of 0.18 per kWh.
[E]
Create custom conversion
Open the dialog to add a conversion or another validity range.
[F]
Pencil icon
Open a custom range for editing, change its settings in the dialog, then select Save.
[G]
Delete icon
Delete the custom range immediately, without confirmation. Deleting its last range also removes the custom conversion.
[H]
Custom emissions range
Apply a factor to express values in the configured emissions unit. Use an appropriate destination unit and approved factor for your calculation.
Custom Conversion Settings
Select Create custom conversion [E] in the conversion list. ▷ The Custom conversion dialog opens.
Enter the conversion settings using the field reference below.
Select Save [G] in the dialog. ▷ The saved range appears in the corresponding conversion group.

[A]
Unit
Select the destination unit, such as MWh, a currency for cost, or an appropriate emissions unit.
[B]
Purpose
Select Unit conversion, Cost, or Emission to determine where the conversion is offered in Analytics.
[C]
Active from
Enter the first date on which the range applies.
[D]
Active to
Enter the last date on which it applies, on or after Active from. Both endpoints are included.
[E]
Factor
Enter the positive multiplier for the source value. For a cost conversion, enter the rate per source unit. The initial value is 1.
[F]
Offset
Enter the constant added after multiplication; leave 0 when no offset is needed.
[G]
Save
Save the conversion directly; the attribute page's separate Save is not required.
[H]
Cancel
Close the dialog without saving its changes.
The calculation is result = value * factor + offset. For example, a factor of 0.18 and offset of 0 convert 1000 kWh to 180 EUR. The figures show demonstration settings, not recommended tariffs or emissions factors.
To add a later rate, use Create custom conversion again with the same Unit and Purpose and a new, non-overlapping date range. For consecutive periods, end one on 31 December and start the next on 1 January. If dates overlap an existing range, adjust them or edit that range instead.
Title language
Use Title language to provide display titles in different interface languages without changing the technical Attribute name. For example, the same power attribute can have the English title Power and the German title Leistung.

Select Title language.
Select Translation [A]. ▷ A language selector and title field are added under Title language and text.
Select the language for the row.
Enter its translated title [B].
Repeat steps 2-4 for each additional language.
Select Save [D]. ▷ The translated titles are saved on the attribute.
To remove a title, select the row's delete icon [C], then select Save [D]. Each language can be selected once.
Pipeline & AR
Use Pipeline & AR to set preferred analytics aggregation settings and choose the attribute's position in the Augmented Reality display.

Aggregation Defaults
Pipeline raster provides preferred settings for new Insight Analytics datapoint series. For example, use an hourly average for a temperature measurement instead of selecting the same aggregation each time you add it to an analytic.
[A]
Mode: None
Leave the preferred mode unspecified for new analytics series.
[A]
Mode: Current value
Start new series with recorded values rather than aggregated values.
[A]
Mode: Aggregated value
Start new series with values calculated over a defined interval. Function and Interval become available.
[B]
Function
Choose an aggregation appropriate to the measurement. For example, Average summarizes temperature over each interval.
[C]
Interval
Choose the time window for each aggregated value. For example, H1 represents one hour. Shorter intervals retain more detail; longer intervals give a coarser view.
Select Pipeline & AR.
Select a Mode [A] under Pipeline raster.
If you select Aggregated value, select a Function [B].
If you select Aggregated value, select an Interval [C].
Select Save [E]. ▷ The preferred aggregation settings are saved on the template attribute.
When you add a new datapoint series to an analytic, Insight Analytics reads these preferences. Updating template defaults leaves settings already configured on existing series unchanged.
You can override Mode, Function, and Interval for an individual series in the Summary Table. This changes the analytic's series settings, not the template defaults. See Aggregations for the aggregation functions.
AR Position
Use Select position [D] under AR Position to choose where the attribute appears in the Augmented Reality display.
No Position
Leave the attribute without an assigned AR position.
Top
Show the attribute at the top.
Bottom Left
Show the attribute at the bottom left.
Bottom Right
Show the attribute at the bottom right.
Select the position [D].
Select Save [E]. ▷ The AR position is saved on the attribute.
Value mapping
Use Value mapping to display readable text for numerical values or ranges. For example, show Idle or Running instead of a raw number.

Each numeric entry is an inclusive upper limit. The displayed text comes from the smallest configured limit greater than or equal to the actual value.
0
Idle
Values less than or equal to 0.
1000
Running
Values greater than 0 and less than or equal to 1000.
For these settings, both 750 and 1000 display Running. A value above 1000 is displayed numerically because it exceeds the highest configured limit. Mapping controls displayed text; use Conversions to convert units.
Select Value mapping.
Select Mapping [A]. ▷ A row with Enter value and Enter result is added.
Enter the numeric upper limit [B].
Enter the text to display [C].
Repeat steps 2-4 for each additional range.
Select Save [E]. ▷ The value mappings are saved on the attribute.
To remove a range, select its delete icon [D], then select Save [E].
Next Steps
Create assets that use the template.
Use the datapoints in Insight Analytics.