Apply Unit, Cost, and Emissions Conversions
Display datapoints in another unit, as a cost, or in a configured emissions unit.
Apply a conversion in Insight Analytics to change the displayed unit or calculate cost or emissions equivalents. The conversion changes the displayed results, not the original recorded readings.
Prerequisites
You can open an Analytic and enable Config mode.
The selected datapoint has a source unit and recorded data for the period you want to analyse.
A conversion exists for that source unit, destination unit, and purpose. See Conversions in the attribute configuration to inspect or configure one.
Convert a Single Datapoint
Open Insight Analytics.
Open the Analytic you want to configure.
Enable Config mode.
Select Single Datapoint under Analytics type.
Select the datapoint in the Location/System tree.
Select a time period covered by the conversion's active ranges.
Select the required purpose under Emissions/cost.
Select the required conversion under Unit conversion. ▷ The chart updates its values and output unit.
Off
Ordinary display-unit conversions
Select kWh-to-MWh to display energy in MWh. Off does not disable ordinary unit conversion.
Cost
Conversions with purpose Cost
Select a configured conversion to a currency such as EUR.
Emission
Conversions with purpose Emission
Select a conversion to the appropriate configured emissions unit.
Choose the purpose first, then the conversion. Changing the purpose clears a conversion that is no longer available. Select None under Unit conversion to remove the selected conversion.
Conversions are available with Current value and Aggregated value. For aggregated data, also check the Function and Interval in the Analytics Configuration bar.
In the display-unit example below, Unit conversion [A] changes kWh to MWh while Emissions/cost is Off [B]. The Stats values [C] use the selected conversion.

Cost Example
Select Cost [A] under Emissions/cost.
Select a configured currency conversion under Unit conversion [B]. ▷ The chart uses the selected conversion, and the Cost column [C] shows the converted result.

Emissions Example
Select Emission [A] under Emissions/cost.
Select the required emissions conversion under Unit conversion [B]. ▷ The chart uses the selected conversion, and the Emissions column [C] shows the converted result.

The example uses the configured destination unit kgCO2/kWh. It illustrates the controls, not a recommended emissions factor or a verified emissions mass total. Use the approved destination unit and factor for your calculation.
Convert Individual Series
For Multiple Datapoints, use the selector on each datapoint's table row. The Unit conversion selector in the configuration bar is disabled for this Analytics type.
Enable Config mode.
Select Multiple Datapoints under Analytics type.
Select the datapoints you want to compare.
Select the analysis period.
Select the required Emissions/cost purpose in the configuration bar.
Open the Conversion tab below the chart.
Select a Unit conversion on the intended datapoint's row. ▷ That series uses the selected conversion.
Repeat the selection for each other series you want to convert.
Each selector offers conversions for its own datapoint's source unit and the selected purpose. Check the output units and chart axes before comparing series; a series left at None remains unconverted.
In the example below, Multiple Datapoints [A] is selected. The first row converts kWh to MWh [B]; the second row remains at None with a disabled selector [C]. If a selector is disabled, check that datapoint's source unit and the available conversions.

Review Converted Results
Open the Conversion tab to review the active purpose. With Cost and a selected cost conversion, the Cost column contains the converted result. With Emission and a selected emissions conversion, the Emissions column contains the result. A column that does not apply shows -.
Open Stats to review Min, Average, and Max for each series using the selected conversion. The chart's aggregation function and interval still determine how its plotted values are calculated. See the Summary Table.
Check the output unit, period, factor, offset, and active dates if a result is unexpected. Use appropriate approved rates and destination units. Demonstration settings are not recommended tariffs or emissions factors; in particular, an emissions intensity unit must not be interpreted as a verified emissions mass total.
Next Steps
Configure conversion ranges to add a new rate period or correct existing settings.
Review Analytics types for the other available comparison views.
Last updated